Voltage Drop in Cables Explained

The cable is a resistor

Every conductor resists, and a cable run is two resistors in series with the load, one in each direction. The load current flowing through that resistance drops voltage along the way, by Ohms law, so the equipment at the far end sees less than the supply. The drop grows in direct proportion to current and to length, and falls with the conductors cross section. Copper resists less than aluminium of the same size, about 1.68 against 2.82 in units of ten to the minus eight ohm metres, which is why aluminium cables are sized a step or two larger. Three phase runs drop less per ampere than single phase for the same power, one of their quiet advantages, the factor being root three rather than two in the formula.

Limits and why they exist

Wiring regulations cap the drop, commonly at 3 percent for lighting and 5 percent for other uses from the origin of the installation, because the consequences are practical, not cosmetic. Motors are the sensitive load: torque falls with the square of voltage, so a motor at 90 percent voltage delivers only 81 percent torque, starts reluctantly, draws more current for the same work and runs hotter. Lamps dim and shift colour. Electronics with regulated supplies tolerate more, until they suddenly do not. There is also an efficiency angle: the dropped volts times the current is power burned in the cable, pure loss, paid for every hour the load runs. On a long heavily loaded run, the lifetime cost of that loss can exceed the price of the next cable size up.

Working the trade off

The designer has three levers: bigger cable, shorter route, or higher voltage. Bigger cable is the usual answer, and the voltage drop check, not the current carrying capacity, is what sizes most long runs: a cable chosen purely for ampacity can be hopelessly small for drop over 100 metres. Shortening the route or moving the distribution board closer is free drop reduction where the layout allows. Raising the voltage is the structural fix: the same power at twice the voltage needs half the current and suffers a quarter of the percentage drop, which is why power crosses countries at hundreds of kilovolts. Two warnings complete the picture. Conductors run hot in service and resistance rises about 0.4 percent per degree for copper, so a drop calculated cold understates the running figure. And on large cables, inductive reactance adds its own drop that the simple resistance formula omits.

Put it into practice

The free calculator that goes with this guide:

Voltage drop calculator